4 X 4 & IP Hydant Pit Valves

Source: Carter Ground Fueling Co.
The Carter Model 60554 Hydrant Pit Valve is a family of valves that includes lanyard, air or dual air/lanyard operated pilot valves, with the latter available with a defueling option
The Carter Model 60554 Hydrant Pit Valve is a family of valves that includes lanyard, air or dual air/lanyard operated pilot valves, with the latter available with a defueling option.

The basic hydrant pit valve consists of three basic parts, lower valve assembly, upper valve assembly (or API outlet adapter) and the pilot valve. The lower valve assembly contains an isolation valve which will allow the removal and servicing of the upper valve assembly and the pilot valve assembly while the pit valve is under pressure. (See service manual SM60554 for proper instructions).

An option is also available to conform the valve to the IP Standard by adding the appropriate 6-inch inlet flange adapter. The outlet conforms to the API Bulletin 1584 Standard.

The standard valve is provided with a new 2-piece upper adapter assembly with a replaceable stainless steel API connecting ring.

The Model 60554 Hydrant Pit Valve is designed to minimize the propagation of surge pressure shocks into the upstream piping system during closure of the valve.

Features

  • NEW two-piece upper half standard, replaceable API outlet adapter of stainless steel per API Bulletin 1584. Ductile iron and all stainless uppers optional.
  • Standard inlet flange mates with 4-inch 150 lb. ANSI flange.
  • Optional inlet flange mates with 6-inch, 300 lb. ANSI flange making valve conform to the IP Standard.
  • Closing time is 2-5 seconds.
  • Lanyard, air or dual air/lanyard operated pilot valve available (for small or large pit applications).
  • Servicing valve standard provides means to remove the upper valve assembly and pilot valve assembly with the unit under pressure.
  • 10 or 20-mesh screen options available.
  • Dual pilot adds true deadman backup to coupler, same as air operated pilot. Hydrant valve is automatically closed at the end of the refueling operation.
  • All seals are field replaceable.
  • Large pressure equalizing valve in the outlet is standard.
  • Defueling capability optional with any air or dual air/lanyard operated pilot.
  • Stone guard optional with 6-inch inlet flange option.
  • Ductile iron epoxy coated for corrosion protection
  • Main piston well guided to minimize piston seal wear.

Carter Ground Fueling Co., 671 West 17th Street, Costa Mesa, CA 92627-3605. Tel: 949-548-3421; Fax: 949-631-2673.